Indoor Air Quality' Assessment Page 2
Stuxwesant Hiah School (M477) ATC Project No. 15-19125-0246
The assessment was perfonned consistent with generally accepted indoor air quality assessment
■ practices. As with all such assessments, there were inherent limitations created by constraints of
time, operational and work practice variability, variations in indoor air quality^ parameters and
sampling and analytical accuracy. The results of the sampling represent conditions found on the
dates of the survey and may not represent conditions found at other times. The information
presented in this report should be used by the BOE as a guide to assess the need for further
improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings,
such as offices and schools. For the real-time data collected, ATC uses the commonly accepted
guidelines cited in the following publications:
Ventilalion for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation.
Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality
will be achieved at all times.
TABLEI
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL AGENCY OR
. X. ' .
ORGANIZATION iti
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2) above background level
Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in
(CO)_____________ ASHRAE 62)
Respirable 65 micrograms per cubic meter USEPA NPAAQS
Particulates (PM2.5) of air (pg/m^) 24-hour average
Temperature Summer: 73-79°F at 50% RH ASHRAE 55
Winter: 68-75 °F at 50% RH
Relative Humidity 30 - 60 % ASHRAE 55
Total Volatile 1 ppm
Organic Compounds AIHA
(TVOC)
USEPA = United States Environmental Protection Agency
NPA\QS = National Primary Ambient-Air Quality Standard
AULA. = American Industrial Hygiene Association