NYC-WTC_000309219
September 2002 IAQ report for PS 124M school.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements at PS 124M prior to school start.
NYC-WTC_000309201–000309204OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr Bernard P Orlan September 11, 2002 Indoor Air Quality Assessment Page 2 PS 124 M ATCProiectNo 15-19125-0350
The results of the sampling represent conditions found on the date of the survey and may not represent conditions found at other times The information presented in this report should be used by the DOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality m non-industnal buildings, such as offices and schools For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-200J), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992), Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times The ASHRAE standards are designed for buildings with mechanical HVAC systems, they are not intended for naturally-ventilated buildings.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter' USEPA NPAAQS . Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer. 73-79°F at 50% RH ASHRAE 55 Winter. 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = Amencan Industnal Hygiene Association
CITY_21MC1OO_OO3O41677
NYC-WTC_000309202
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000309219
September 2002 IAQ report for PS 124M school.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309210
Indoor air quality report distributed to NYC DOE for PS 124M.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239839
Report of indoor air quality measurements collected at PS 124M in September 2002 to verify acceptable air conditions.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175529
Report from ATC Associates detailing indoor air quality measurements collected at a New York City Department of Education school.
9 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309803
ATC indoor air quality memo regarding PS 42M measurements.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309812
DOE IAQ memo for PS 42M measurements conducted Sept 4, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309794
DOE-requested indoor air quality measurements at PS 42M, Sept 2002.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309350
Indoor air quality measurements at PS 2M, Aug 23, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350145
ATC September 4-6, 2002 indoor air measurements at PS 42M for DOE.
9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309359
Memo regarding IAQ measurements at PS 2M, Aug 23, 2002.
9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239058
Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 126M on August 28, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309368
Memo noting indoor air quality measurements at PS 2M, Aug 2002.
9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000175529
Report from ATC Associates detailing indoor air quality measurements collected at a New York City Department of Education school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309210
Indoor air quality report distributed to NYC DOE for PS 124M.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309368
Memo noting indoor air quality measurements at PS 2M, Aug 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239839
Report of indoor air quality measurements collected at PS 124M in September 2002 to verify acceptable air conditions.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000310159
ATC indoor air quality measurements at a DOE school for August 27, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309359
Memo regarding IAQ measurements at PS 2M, Aug 23, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000309219
September 2002 IAQ report for PS 124M school.
Similar indexed content
NYC-WTC_000309210
Indoor air quality report distributed to NYC DOE for PS 124M.
Similar indexed content
NYC-WTC_000239839
Report of indoor air quality measurements collected at PS 124M in September 2002 to verify acceptable air conditions.