Mr. Bernard P Orlan August 29, 2002 Indoor Air Quality Assessment Page 2 PS IM ATCProiectNo 15-19125-0340
The results of the sampling represent conditions found on the date of the survey and may not represent conditions found at other times. The information presented in this report should be used by the DOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality m non-industnal buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications.
Ventilation for Acceptable Indoor Atr Quality (ASHRAE 62-2001), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA). 2 Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLEI TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS)___________ Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter; 68-75°F at 50% RH Relative Humidity 30-60% ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = Amencan Industrial Hygiene Association
CITY_21MC100_011 095172
NYC-WTC_000310160
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000309455
ATC report on indoor air quality measurements at Alfred E. [name] (P.S. IM), Aug 2002.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309465
ATC IAQ measurements report for Alfred E. [name] (P.S. IM), Aug 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000316573
ATC memo describing IAQ measurements conducted at the DOE facility.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350024
Memo/letter from ATC regarding DOE project PS IM at 28-11 [name], Aug 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000238526
Report detailing indoor air quality measurements collected at P.S. 2M for the New York City Department of Education.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000316563
ATC notes on indoor air quality measurements taken at a NYC school.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000316583
ATC memo documenting IAQ measurements at the DOE site in Aug 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000316199
ATC report of IAQ measurements at the referenced NYC DOE school, August 2002.
10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328522
Indoor air quality IAQ report for Dr. [name] at J.H.S. 131M; August 22, 2002 measurements.
10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000222482
ATC Associates letter submitting indoor air quality measurement results collected on April 17, 2002, at P.S. 89M for the NYC Board of Education.
9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328765
Indoor air quality measurements at DeSoto School PS 130M.
10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392743
ATC IAQ measurements conducted at P.S. 89M for NYC BOE.
9 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000309359
Memo regarding IAQ measurements at PS 2M, Aug 23, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309368
Memo noting indoor air quality measurements at PS 2M, Aug 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309803
ATC indoor air quality memo regarding PS 42M measurements.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309794
DOE-requested indoor air quality measurements at PS 42M, Sept 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309350
Indoor air quality measurements at PS 2M, Aug 23, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175150
Letter and report from ATC Associates regarding indoor air quality measurements collected at DeSoto School in August 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000309455
ATC report on indoor air quality measurements at Alfred E. [name] (P.S. IM), Aug 2002.
Similar indexed content
NYC-WTC_000309465
ATC IAQ measurements report for Alfred E. [name] (P.S. IM), Aug 2002.
Similar indexed content
NYC-WTC_000316573
ATC memo describing IAQ measurements conducted at the DOE facility.
Similar indexed content
NYC-WTC_000350024
Memo/letter from ATC regarding DOE project PS IM at 28-11 [name], Aug 2002.
Similar indexed content
Report detailing indoor air quality measurements collected at P.S. 2M for the New York City Department of Education.
Similar indexed content