Mr. Bernard P Orlan September 11, 2002 Indoor Air Quality Assessment Page 3 PS 124 M ATCProiectNo 15-19125-0350
Real-Time Environmental Measurements
ATC collected fifty (50) sets of real-time environmental measurements consisting of forty-eight (48) m the school building and two (2) outdoors. All floors of the school were surveyed Field data sheets are found m the Attachment Readings were collected during school hours' The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 75 6 to 83.1 °F. Eighteen (18) of the indoor temperature measurements were above the range of 73 to 79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season The outdoor temperature measurements were 76 4 and 79 7 °F.
Relative Humidity
The relative humidity indoors ranged from 30 6 percent to 50.3 percent All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 , percent for occupant comfort The outdoor relative humidity measurements were 40.3 and 46 9 percent The high ambient relative humidity likely contnbuted to the elevated particulate levels reported below.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 760 ppm to 1302 ppm All indoor measurement for CO2 were below the ASHRAE Standard 62-2001 recommended maximum concentration of <700 ppm above the background level The average outdoor (background) CO2 concentration was 670 ppm Therefore, the maximum acceptable level of CO2 at this location was 1370 ppm (background level + 700 ppm) Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2 ppm for both readings
Respirable Particulates (PM2
Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 64 pg/m^. Fourteen (14) of the indoor measurements collected for PM2.5 were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The two outdoor respirable particulate concentrations were 32 pg/m^ and 52 pg/m^ with an average of 42 pg/m3.
CITY_21MC100_003041678
NYC-WTC_000309203
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000309219
September 2002 IAQ report for PS 124M school.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309210
Indoor air quality report distributed to NYC DOE for PS 124M.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239839
Report of indoor air quality measurements collected at PS 124M in September 2002 to verify acceptable air conditions.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175529
Report from ATC Associates detailing indoor air quality measurements collected at a New York City Department of Education school.
9 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309803
ATC indoor air quality memo regarding PS 42M measurements.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309812
DOE IAQ memo for PS 42M measurements conducted Sept 4, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309794
DOE-requested indoor air quality measurements at PS 42M, Sept 2002.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309350
Indoor air quality measurements at PS 2M, Aug 23, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350145
ATC September 4-6, 2002 indoor air measurements at PS 42M for DOE.
9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309359
Memo regarding IAQ measurements at PS 2M, Aug 23, 2002.
9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239058
Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 126M on August 28, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309368
Memo noting indoor air quality measurements at PS 2M, Aug 2002.
9 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000239839
Report of indoor air quality measurements collected at PS 124M in September 2002 to verify acceptable air conditions.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309210
Indoor air quality report distributed to NYC DOE for PS 124M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309219
September 2002 IAQ report for PS 124M school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175529
Report from ATC Associates detailing indoor air quality measurements collected at a New York City Department of Education school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309794
DOE-requested indoor air quality measurements at PS 42M, Sept 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309812
DOE IAQ memo for PS 42M measurements conducted Sept 4, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000309219
September 2002 IAQ report for PS 124M school.
Similar indexed content
NYC-WTC_000309210
Indoor air quality report distributed to NYC DOE for PS 124M.
Similar indexed content
NYC-WTC_000239839
Report of indoor air quality measurements collected at PS 124M in September 2002 to verify acceptable air conditions.
Similar indexed content
NYC-WTC_000175529
Report from ATC Associates detailing indoor air quality measurements collected at a New York City Department of Education school.
Similar indexed content
NYC-WTC_000309803
ATC indoor air quality memo regarding PS 42M measurements.
Similar indexed content