Mr. Bernard P. Orlan March 8. 2002
Indoor Air Quality Assessment Page 3
P. S. 150M_________________ ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
A FC collected forty (40 ) sets of real-time environmental measurements consisting of thirty (30 )
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. Thc.re results are described below'.
f'leld data sheets are found in Attachment 1. Readings began at 2;00 P.M. and concluded at
approximately 3;35 P.M
Ttimperature
Indoor dry bulb temperature measurements ranged from 71.OT to 77.8°F. Eighteen (18) of the
measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as
recommended by the ASFtRAE Standard 55-1992 during the heating season (wintertime
conditions). The outdoor temperature measurements ranged from 66.0 to 6Y3"'F.
Relative HumidUy
The relative humidity indoors ranged from 20.1 to 25.1 percent. All of the measurements were
below the .ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 17.4 to 20.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 574 ppm to 810 ppm. All of the COn
measurements were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 493 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1193 ppm (background level + 700 ppm). Levels above the recommended
maximum co not indicate a health risk. Carbon dioxide measurements are used a.s an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentralion
Carbon m.onoxide concentrations were 0 ppm for the interior readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CQ concentration was 0
ppm for all collected readings.
Rexpirahle Particulates (PM2,
Respirable particulate concentrations* indoors ranged between 25 ug/m^ to 37 pg/m^. None of
the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PMr.s
concentration for the entire school building was approximately 31 pg/m3. The PM2.5 average
concentration was below the USEPA recommended concentration of 43 pg/m3 for sensitive
individuals / children. The outdoor respirable particulate concentration measurements ranged
from 38 to 43 pg/m^ with an average of 40 pg/m^.