Mr. Bernard P. Orlan March 11,2002 Indoor Air Quality Assessment Page 3 P. S. 150M ________ ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded at approximately 3:35 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.8 °F to 76 °F. Fifteen (15) of the indoor temperature measurements were above and fifteen (15) were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 54.5 to 56 °F.
Relative Humidity
The relative humidity indoors ranged from 30 to 53.9 percent. All of the indoor measurements for relative humidity were within the ASHRAE-reconunended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 44 to 47 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 621 ppm to 903 ppm. All of the CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 555 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1255 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations were 1 ppm for the interior readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm for all collected readings.
Respirable Particulates (PM2^5)
Respirable particulate concentrations* indoors ranged between 67 gg/m^ to 96 gg/m^. All of the measurements were above the NPAAQS of 65 gg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 87 gg/m^. All of the instantaneous indoor and outdoor readings were above the USEPA recommended concentration
CITY_21MC100_0 04151915
NYC-WTC_000300772
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000300802
IAQ measurements report for PS 150M prior to re-occupancy, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300673
ATC IAQ measurements at PS 150M for pre-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300820
ATC IAQ measurements report for PS 150M, March 19, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410443
IAQ report for PS 150M following measurements on Feb 12, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178754
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on May 17, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374800
IAQ measurements collected at PS 150M for re-occupancy assessment, May 17, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253607
ATC IAQ measurements at NY school, BOE pre-occupancy purposes.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253603
Indoor air quality measurements at P.S. 150M for BOE pre-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375509
IAQ measurements at PS 150M prior to re-occupancy, March 19, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253595
ATC IAQ measurements at the referenced NYC school for BOE pre-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249756
ATC indoor air quality report for PS 150M, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375457
Indoor air quality report for P.S. 150M dated Feb 4, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000253619
Indoor air quality measurements at the referenced school requested by BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375473
Indoor air quality measurements collected Feb 7, 2002 for PS 150M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410515
ATC IAQ measurements at PS 150M before occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249756
ATC indoor air quality report for PS 150M, April 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374904
ATC IAQ measurements at school prior to re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253811
ATC IAQ measurements at PS 150M prior to re-occupancy; results documented.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000300802
IAQ measurements report for PS 150M prior to re-occupancy, March 2002.
Similar indexed content
NYC-WTC_000300673
ATC IAQ measurements at PS 150M for pre-occupancy evaluation.
Similar indexed content
NYC-WTC_000300820
ATC IAQ measurements report for PS 150M, March 19, 2002.
Similar indexed content
NYC-WTC_000410443
IAQ report for PS 150M following measurements on Feb 12, 2002.
Similar indexed content
NYC-WTC_000178754
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on May 17, 2002.
Similar indexed content