NYC-WTC_000249776
ATC IAQ measurements report for PS 150M, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗ATC indoor air quality report for PS 150M, April 2002.
NYC-WTC_000249756–000249759OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 18, 2002 Indoor Air Quality Assessment Page 3 P. S. 150M_______________ ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at approximately 1:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 77.2°F to 81.4°F. Six (6) of the indoor measurements for temperature were above and twenty-four (24) measurements were within the range of 73 to 79 °F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 84.1 °F to 87.0°F.
Relative Humidity
The relative humidity indoors ranged from 34.8 to 42.8 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 40.2 to 45 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 667 ppm to 1048 ppm. All of the CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 526 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1226 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations was 2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 6 ppm for all collected readings.
Respirable Particulates (PM2_s) PP^-
Respirable particulate concentrations* indoors ranged between 60 pg/m^ to 90 pg/m^. Twenty seven (27) of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ for 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the instantaneous indoor measurements were above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The average PM2.5 concentration for the entire school building was approximately 79 pg/m^. The outdoor
CONFIDENTIAL, CITY_21MC100_0 05759580 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000249758
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000249776
ATC IAQ measurements report for PS 150M, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177954
Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177942
Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253603
Indoor air quality measurements at P.S. 150M for BOE pre-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374680
Indoor air quality report for P.S. 150M, Greenwich Street, Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249904
ATC IAQ report for PS 150M, May 22, 2002, prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177946
Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253607
ATC IAQ measurements at NY school, BOE pre-occupancy purposes.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253595
ATC IAQ measurements at the referenced NYC school for BOE pre-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249848
Indoor air quality measurements collected May 9, 2002 for PS 150M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374692
IAQ measurements for P.S. 150M prior to re-occupancy, Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374816
IAQ report detailing measurements at PS 150M for BOE re-occupancy review, May 21, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000410515
ATC IAQ measurements at PS 150M before occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253619
Indoor air quality measurements at the referenced school requested by BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375473
Indoor air quality measurements collected Feb 7, 2002 for PS 150M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249956
ATC IAQ measurements at P.S. 150M, prior to occupancy, BOE referenced.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249776
ATC IAQ measurements report for PS 150M, April 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253839
ATC IAQ measurements at PS 150M for pre-occupancy evaluation.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000249776
ATC IAQ measurements report for PS 150M, April 2002.
Similar indexed content
Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.
Similar indexed content
Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.
Similar indexed content
NYC-WTC_000253603
Indoor air quality measurements at P.S. 150M for BOE pre-occupancy.
Similar indexed content
NYC-WTC_000374680
Indoor air quality report for P.S. 150M, Greenwich Street, Apr 2002.
Similar indexed content