NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 8, 2002
Indoor Air Cjuality Assessment Page 4
P.S. 150M ATC Project No. 15-19125-0289
* The measurements made during this assessment were instantaneous readings, the NPA.AQS is
a 24-hour average.
TVOC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). Tire outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• I'here was construction work going on in the plaza;
• The school building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concen trations of CO, CO2 and TVOCs were within applicable standards and guidelines;
2. None of the PM2.5 measurements were above the NPAAQS of 65 pg/m^- Two (2)ol' the
outdoor measurements were above the USEPA recommended PM2.5 concentration of 40
pg/m3 for sensitive individuals and children.
3. Eighteen (18) of the temperature measurement were above the range of 68 to 75° F (at 50
percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating
season (wintertime conditions).
4. All indoor measurements of relative humidity were below the ASHRAE recommended range
of 30 to 60 percent for occupant comfort.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or 212.