Mr. Bernard P. Orlan February 4, 2002 Indoor Air Quality Assessment Page 3 RSM50M ATC Project No. 15-I9125-02S9

Real-Time Environmental Measurements

ATC collected forty (40) sets of real-time environmental measurements consisting of thirty-two (32) inside the school building and eight (8) outdoors. All tliree floors of the school building were surveyed. Field data sheets are'found in the Attachment. Readings began at 8:30 A.M. and concluded at approximately 12:30 P.M. The results are described below.

Temperature

Indoor temperature measurements ranged from 69.2°F to 74.1 °F. All measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 41.9 to 43.3°F.

Relative Humidity

The relative humidity indoors ranged from 14.8 to 20.1 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 18.9 to 20.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 402 ppm to 610 ppm. All COg measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 457 ppm. Therefore, the maximum acceptable level of COg at this location was 1157 ppm (background level + 700 ppm). Levels above the recommended maximum do.not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors' is occupant respiration. Tire school building was not occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for the indoor readings. The outdoor CO concentration was 0-1 ppm for all collected readings.

Respirable Particulates (PM2.5)

Respirable particulate concentrations* indoors ranged between 4 ug/m^ to 29 ug/mA None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 8 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged from 4 to 6 pg/m3 with an average of approximately 4 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_2IMC100_002954065

NYC-WTC_000289328

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000289328Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000375449

Indoor air quality measurements collected for BOE re-occupancy evaluation at P.S. 150M.

Similar indexed content

NYC-WTC_000375445

Indoor air quality measurements at P.S. 150M for re-occupancy evaluation.

Similar indexed content

Compare copies and versions →