NYC-WTC_000300629
ATC indoor air quality report for PS 150M related to re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements collected for BOE re-occupancy evaluation at P.S. 150M.
NYC-WTC_000375449–000375452OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan February 4, 2002 Indoor Air Quality Assessment Page 3 P. S. I50M ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty-two (32) inside the school building and eight (8) outdoors. All three floors of the school building were surveyed. Field data sheets are found in the Attachment. Readings began at 8:30 A.M. and concluded at approximately 12:30 P.M. The results are described below.
Temperature
Indoor temperature measurements ranged from 69.2°F to 74.1°F. All measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 41.9 to 43.3°F.
Relative Humidity
The relative humidity indoors ranged from 14.8 to 20.1 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 18.9 to 20.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 402 ppm to 610 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 457 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1157 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was not occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for the indoor readings. The outdoor CO concentration was 0-1 ppm for all collected readings.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 29 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 8 pg/m3. The PM2.5 average concenPation was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged from 4 to 6 pg/m^ with an average of approximately 4 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_002853431
NYC-WTC_000375451
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000300629
ATC indoor air quality report for PS 150M related to re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375445
Indoor air quality measurements at P.S. 150M for re-occupancy evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214370
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 30, 2002, for pre-reoccupancy evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375441
Indoor air quality measurements at P.S. 150M, school building prior to re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000194812
Cover letter for indoor air quality measurements collected at PS150M on February 11, 2002, submitted to the Board of Education.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374784
Indoor air quality measurements at PS 150M for re-occupancy evaluation, May 15, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000398157
IAQ measurements at P.S. 150M prior to re-occupancy; scope and results described.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374964
ATC IAQ measurements at P.S. 150M prior to occupancy; June 21, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253663
IAQ measurement summary for PS 150M school, May 2002, by ATC.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374700
ATC reports IAQ measurements taken April 24, 2002 at P.S. 150M for BOE air quality review.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178726
Letter from ATC Associates providing indoor air quality measurement results collected at P.S. 150M prior to re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300664
ATC indoor air quality measurements at PS 150M prior to re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000375489
Indoor air quality measurements collected Feb 28, 2002 for PS 150M.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289326
IAQ measurements at a school building to assess air quality before re-occupancy.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374724
ATC IAQ measurements at PS 150M for school building re-occupancy assessment, May 1, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375533
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375441
Indoor air quality measurements at P.S. 150M, school building prior to re-occupancy.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300615
ATC indoor air quality measurements at PS 150M prior to re-occupancy.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000300629
ATC indoor air quality report for PS 150M related to re-occupancy.
Similar indexed content
Indoor air quality measurements at P.S. 150M for re-occupancy evaluation.
Similar indexed content
NYC-WTC_000214370
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 30, 2002, for pre-reoccupancy evaluation.
Similar indexed content
Indoor air quality measurements at P.S. 150M, school building prior to re-occupancy.
Similar indexed content
NYC-WTC_000194812
Cover letter for indoor air quality measurements collected at PS150M on February 11, 2002, submitted to the Board of Education.
Similar indexed content