Mr. Bernard P. Orlan March 1, 2002 Indoor Air Quality Assessment Page 3 P. S. 150M ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded at approximately 3:35 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.3 °F to 75.6 °F. Seven (7) of the measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 36 to 38.1 °F.
Relative Humidity
The relative humidity indoors ranged from 12.3 to 19.6 percent. All of the indoor measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 30.1 to 33.3 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 586 ppm to 981 ppm. All of the CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 490 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1190 ppm (background level -t- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations were 0 ppm for the interior readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 0 ppm for all collected readings.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 8 ug/m^ to 20 pg m^. None of the measurements were above the NPAAQS of 65 ug/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 11 pg/m^. The PM2,5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged from 16 to 23 pg/m^ with an average of 16 pg/m^.
CITY_21MC100_002853476
NYC-WTC_000375491
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000375533
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375529
Indoor air quality measurements at P.S. 150M, March 6, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000194816
Cover letter for indoor air quality measurements collected at PS150M on February 15, 2002, submitted to the Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300743
ATC provides IAQ evaluation for PS 150M in Mar 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300705
ATC IAQ measurements at PS 150M before occupancy, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214968
Letter from ATC Associates reporting indoor air quality measurements collected at PS 150M on March 27, 2002, prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300761
ATC IAQ measurements at PS 150M, March 2002; pre-occupancy monitoring.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374676
Indoor air quality report for P.S. 150M, Greenwich Street, Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375501
ATC IAQ measurements at P.S. 150M before re-occupancy, March 25, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410559
Report of IAQ measurements at a NYC school building prior to re-occupancy, March 7, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375441
Indoor air quality measurements at P.S. 150M, school building prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000194820
Cover letter for indoor air quality measurements collected at PS150M on March 4, 2002, submitted to the Board of Education.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300829
IAQ measurements at PS 150M prior to re-occupancy, March 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375481
Indoor air quality measurements collected Feb 11, 2002 for PS 150M.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375533
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410567
IAQ measurements report for PS 150M prior to re-occupancy, March 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375441
Indoor air quality measurements at P.S. 150M, school building prior to re-occupancy.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000375533
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similar indexed content
NYC-WTC_000375529
Indoor air quality measurements at P.S. 150M, March 6, 2002.
Similar indexed content
NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similar indexed content
NYC-WTC_000194816
Cover letter for indoor air quality measurements collected at PS150M on February 15, 2002, submitted to the Board of Education.
Similar indexed content
NYC-WTC_000300743
ATC provides IAQ evaluation for PS 150M in Mar 2002.
Similar indexed content