NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor Air Quality Report, P.S. 150M

Machine-extracted title · confidence 60%

Indoor air quality report for P.S. 150M dated Feb 4, 2002.

NYC-WTC_000375457–000375460
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Beimard P. Orlan Februai7 4, 2002 Indoor Air Quality Assessment Page 3 P. S. 150M ATC Project No. 15-19125-0289

Real-Time Environmental Measurements

ATC collected forty (40) sets of real-time environmental measurements consisting of twenty- nine (29) from inside the school building and eleven (11) from the outdoors. All three floors of the school building were surveyed, - These results are described below.

Field data sheets are found in Attachment 1. Readings began at ll;00 A.M. and concluded at approximately 1:00 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 70.9°F to 79.0°F. Ten (10) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 43.0 to 54.9“F.

Relative Humidity

The relative humidity indoors ranged from 17.4 to 37.5 percent. Only three (3) of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The rest of the measurements were below the recommended range. The outdoor relative humidity measurements ranged from 13.0 to 23.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 550 ppm to 1329 ppm. Only one (1) of the CO2 measurements was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. Tire maximum outdoor (background) CO2 concentration was 585 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1285 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppms for the interior readings. These concentrations were below the NPAAQS/ASEIRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm for all collected readings.

Respirable Particulates (PM2j)

Respirable particulate concentrations* indoors ranged between 12 pg/m^ to 32 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 25 pg/m^. Tire PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive

CITY_21MC100_002853440

NYC-WTC_000375459

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000375459Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →