NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor Air Quality Report, P.S. 150M

Machine-extracted title · confidence 60%

Indoor air quality report for P.S. 150M dated Feb 4, 2002.

NYC-WTC_000375457–000375460
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 4, 2002 Indoor Air Quality Assessment Page 4 P. S. 150M ATC Project No. 15-19125-0289 individuals / children. The outdoor respirable particulate concentration measurements ranged from 16 to 44 pg/m^ with an average of 25 pg/m-.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • There was construction work going on in the plaza; • The school building was occupied at the time of the assessment; • No smoke odor was detected in the building

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were within applicable standards and guidelines; 2. None of the PM2.5 measurements were above the NPAAQS of 65 pg/m^ or above the USEPA recommended PM2.5 concentration of 40 pg/m^ for sensitive individuals and children. 3. Ten (10) temperature measurements were above the range of 68 to 75 0 F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. Twenty-six (26) indoor measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 5. One (1) COj measurement was above the range recommended by ASHRAE 62-1999. All others were below the maximum concentration.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 261 or 212.

Sincerely, Reviewed by: A TC ASSOCIA TES INC.

Yiarmis Efstathiou James R. Cohn, CIH, CSP Project Manager Regional Manager Industrial Hygiene Division

CITY_21MC100_002853441

NYC-WTC_000375460

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000375460Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →