NYC-WTC_000300673
ATC IAQ measurements at PS 150M for pre-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality report for P.S. 150M dated Feb 4, 2002.
NYC-WTC_000375457–000375460OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan February 4, 2002 Indoor Air Quality Assessment Page 2 P. S. 150M ATC Project No. 15-19125-0289
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not .represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Tbermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED ■1 ________________________________________________________________________________________________________________________________ ■ ■
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO)______________ USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (ug m3) 24-hour average 40 pg/m j 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_002853439
NYC-WTC_000375458
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000300673
ATC IAQ measurements at PS 150M for pre-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289334
ATC indoor air quality report for PS 150M; measurements on Feb 4, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300633
ATC IAQ report covering measurements at PS 150M for re-occupancy
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178754
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on May 17, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300820
ATC IAQ measurements report for PS 150M, March 19, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374800
IAQ measurements collected at PS 150M for re-occupancy assessment, May 17, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178734
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on April 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410443
IAQ report for PS 150M following measurements on Feb 12, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375521
IAQ measurements at PS 150M prior to re-occupancy, March 12, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300770
ATC IAQ measurements at PS 150M on Mar 8, 2002 for BOE school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253607
ATC IAQ measurements at NY school, BOE pre-occupancy purposes.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375509
IAQ measurements at PS 150M prior to re-occupancy, March 19, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000375481
Indoor air quality measurements collected Feb 11, 2002 for PS 150M.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245367
ATC Associates provides IAQ measurements for P.S. 89M per NYC BOE request.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249964
Indoor air quality measurements at P.S. 150M to assess before re-occupancy.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253711
ATC IAQ measurements for PS 150M prior to re-occupancy.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236977
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373529
Indoor air quality report for P.S. 234M, January 22, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000300673
ATC IAQ measurements at PS 150M for pre-occupancy evaluation.
Similar indexed content
NYC-WTC_000289334
ATC indoor air quality report for PS 150M; measurements on Feb 4, 2002.
Similar indexed content
NYC-WTC_000300633
ATC IAQ report covering measurements at PS 150M for re-occupancy
Similar indexed content
NYC-WTC_000178754
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on May 17, 2002.
Similar indexed content
NYC-WTC_000300820
ATC IAQ measurements report for PS 150M, March 19, 2002.
Similar indexed content