Mr. Bernard P. Orlan February 4. 2002 Indoor Air Quality Assessment Page 2 P. S. 150M ATC Proiect No. 15-19125-0289
Tae assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. Tlie results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in cument indoor air quality control activities.
EX'ALUATIQN CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-induslrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality lASHRAE 62-199Q), .American Society' ol Heating, Refrigerating, and Air-Conditioning Engineer;; (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one., some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED PARAMETER .. t TARGET LEVEL .4AGENGM/OR2iii,i. c V, st is ■ ORGANIZATION Carbon Dicxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/md 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH “\SHRAE55 ““ Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHR.AE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United Stales Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_0 02954064
NYC-WTC_000289327
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000300629
ATC indoor air quality report for PS 150M related to re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375449
Indoor air quality measurements collected for BOE re-occupancy evaluation at P.S. 150M.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375445
Indoor air quality measurements at P.S. 150M for re-occupancy evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289334
ATC indoor air quality report for PS 150M; measurements on Feb 4, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289354
Report of indoor air quality measurements conducted February 8, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289418
IAQ measurements at PS 150 M around March 21-27, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374708
ATC IAQ measurements at P.S. 150M for BOE air quality assessment, April 26, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374668
Indoor air quality assessment report for P.S. 150M, Greenwich Street, Apr 2002.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253619
Indoor air quality measurements at the referenced school requested by BOE.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375457
Indoor air quality report for P.S. 150M dated Feb 4, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214370
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 30, 2002, for pre-reoccupancy evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374784
Indoor air quality measurements at PS 150M for re-occupancy evaluation, May 15, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000374852
IAQ measurements at PS 150M for re-occupancy evaluation, May 29, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253571
ATC IAQ measurements at P.S. 150M for pre-occupancy evaluation by BOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214370
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 30, 2002, for pre-reoccupancy evaluation.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374668
Indoor air quality assessment report for P.S. 150M, Greenwich Street, Apr 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000218569
Letter reporting indoor air quality measurements collected at P.S. 89M on February 11, 2002, to evaluate conditions prior to re-occupancy.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000300629
ATC indoor air quality report for PS 150M related to re-occupancy.
Similar indexed content
Indoor air quality measurements collected for BOE re-occupancy evaluation at P.S. 150M.
Similar indexed content
Indoor air quality measurements at P.S. 150M for re-occupancy evaluation.
Similar indexed content
NYC-WTC_000289334
ATC indoor air quality report for PS 150M; measurements on Feb 4, 2002.
Similar indexed content
NYC-WTC_000289354
Report of indoor air quality measurements conducted February 8, 2002.
Similar indexed content