Mr. Bernard P. Orlan February 4, 2002 Indoor Air Quality Assessment Page 3 P. S. 15QM ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty-two (32) inside the school building and eight (8) outdoors. All three floors of the school building were surveyed. Field data sheets are found in the Attachment. Readings began at 8:30 A.M. and concluded at approximately 12:30 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 69.1 °F to 80.5°F. One (1) measurement was above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 37.5 to 45.5°F.
Relative Humidity
The relative humidity indoors ranged from 14.6 to 22.3 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 13.2 to 20.3 percent.
Carbon Dioxide Concentration
Carbon dioxide concenfrations indoors ranged from 400 ppm to 630 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 478 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1178 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of COg indoors is occupant respiration. The school building was not occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for the indoor readings. The outdoor CO concentration was 0-1 ppm for all collected readings.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 33 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 9 pg/m^. The PM2,5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged from 4 to 6 pg/m3 with an average of 5 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_002954056
NYC-WTC_000289320
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000375445
Indoor air quality measurements at P.S. 150M for re-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410459
ATC IAQ report for PS 150M; measurements conducted Feb 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375449
Indoor air quality measurements collected for BOE re-occupancy evaluation at P.S. 150M.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314914
Indoor air quality measurements collected at P.S. 234M per BOE program.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300629
ATC indoor air quality report for PS 150M related to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289334
ATC indoor air quality report for PS 150M; measurements on Feb 4, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375457
Indoor air quality report for P.S. 150M dated Feb 4, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249708
Indoor air quality measurements at PS 150M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000398157
IAQ measurements at P.S. 150M prior to re-occupancy; scope and results described.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253663
IAQ measurement summary for PS 150M school, May 2002, by ATC.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374732
ATC IAQ measurements at PS 150M; BOE re-occupancy evaluation, May 2, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300655
ATC IAQ field report for PS 150M, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000375445
Indoor air quality measurements at P.S. 150M for re-occupancy evaluation.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253583
ATC IAQ measurements collected at the referenced school for BOE pre-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375529
Indoor air quality measurements at P.S. 150M, March 6, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410467
IAQ measurements collected Feb 15, 2002 at PS 150M for BOE evaluation.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383828
Indoor air quality measurements collected March 12, 2002 at PS89M for BOE evaluation.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300673
ATC IAQ measurements at PS 150M for pre-occupancy evaluation.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements at P.S. 150M for re-occupancy evaluation.
Similar indexed content
NYC-WTC_000410459
ATC IAQ report for PS 150M; measurements conducted Feb 14, 2002.
Similar indexed content
Indoor air quality measurements collected for BOE re-occupancy evaluation at P.S. 150M.
Similar indexed content
NYC-WTC_000314914
Indoor air quality measurements collected at P.S. 234M per BOE program.
Similar indexed content
NYC-WTC_000300629
ATC indoor air quality report for PS 150M related to re-occupancy.
Similar indexed content