Indoor Air Quality Report, P.S. 150M

Machine-extracted title · confidence 60%

Indoor air quality measurements at P.S. 150M for re-occupancy evaluation.

NYC-WTC_000375445–000375448
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 4, 2002 Indoor Air Quality Assessment Page 3 P.S. 150M ATC Project No. 15-19125-0289

Real-Time Environmental Measurements

ATC collected forty (40) sets of real-time environmental measurements consisting of thirty-two (32) inside the school building and eight (8) outdoors. All three floors of the school building were surveyed. Field data sheets are found in the Attachment. Readings began at 8:30 A.M. and concluded at approximately 12:30 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 69.1°F to 80.5°F. One (1) measurement was above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 37.5 to 45.5°F.

Relative Humidity

The relative humidity indoors ranged from 14.6 to 22.3 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 13.2 to 20.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 400 ppm to 630 ppm. All COg measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 478 ppm. Therefore, the maximum acceptable level of COg at this location was 1178 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of COg indoors is occupant respiration. The school building was not occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for the indoor readings. The outdoor CO concentration was 0-1 ppm for all collected readings.

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged between 4 (ug/m^ to 33 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 9 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged from 4 to 6 pg/m^ with an average of 5 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_002853422

NYC-WTC_000375447

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000375447Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

IAQ report for PS 89M, Apr 2002 · Box unavailable

NYC-WTC_000220647

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 8, 2002.

12 shared non-person entities · 1 shared topics · similarity 0.998

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000375449

Indoor air quality measurements collected for BOE re-occupancy evaluation at P.S. 150M.

Similar indexed content

NYC-WTC_000375441

Indoor air quality measurements at P.S. 150M, school building prior to re-occupancy.

Similar indexed content

IAQ report, May 15, 2002

NYC-WTC_000398157

IAQ measurements at P.S. 150M prior to re-occupancy; scope and results described.

Similar indexed content

Compare copies and versions →