Mr. Bernard P. Orlan April 15, 2002
Indoor Air Quality Assessment Page 3
P. S. 15QM ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30)
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at
approximately 1:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.6°F to 74.8°F. All of the indoor
measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as
recommended by the ASHRAF Standard 55-1992 during the heating season (wintertime
conditions). The outdoor temperature measurements ranged from 55.8 °F to 57.3 °F.
Relative Humidity
The relative humidity indoors ranged from 29.0 to 33.4 percent. One (1) of the measurements
was below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The
outdoor relative humidity measurements ranged from 39.4 to 44.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 690 ppm to 909 ppm. All of the CO2
measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 488 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1188 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations ranged from 1 ppm to 2 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 2
ppm for all collected readings.
Respirable Particulates (PM2,§) ppm.
Respirable particulate concentrations* indoors ranged between 18 pg/m^ to 32 pg/m^. None of
the indoor and outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the
USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The
average PM2.5 concentration for the entire school building was approximately 25 pg/m^. The
outdoor respirable particulate concentration measurements ranged from 29 to 38 pg/m3 with an
average of 34 pg/m^.