Mr. Bernard P. Orlan February 13, 2002 Indoor Air Quality Assessment Page 3 P. S. 150M ATC Project No. 15-19125-0289

Real-Time Environmental Measurements

ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 11:00 A.M. and concluded at approximately 4:00 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 68.3°F to 75.7°F. Three (3) of the measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 36.9 to 43.0°F.

Relative Humidity

The relative humidity indoors ranged from 19.0 to 33.4 percent. Only one (1) measurement was within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other measurements were below the recommended range. The outdoor relative humidity measurements ranged from 19.5 to 26.0 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 509 ppm to 1299 ppm. One (1) of the CO2 measurements was above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 473 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1173 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppms for the interior readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm for all collected readings.

Respirable Particulates (PM2j)

Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 19 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 10 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive

CITY_21MC100_004151798

NYC-WTC_000300675

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000300675Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000375457

Indoor air quality report for P.S. 150M dated Feb 4, 2002.

Similar indexed content

Compare copies and versions →