samples were below the detection limits after the first cleaning, no additional samples were
collected for calcite.
Cristobalite
Before Cleaning Samples - There were three pre-cleaning wipe samples collected. All three
samples were below the detection limit.
Post P‘ Cleaning Samples - There were two air samples and four wipe samples collected
after the first cleaning. All of the samples were below the detection limit. Since all of the
samples were below the detection limit for cristobalite, no additional samples were collected.
Tridymite
Before Cleaning Samples - There were three pre-cleaning wipe samples collected. Two of
the three samples were above the detection limit and the third was below the detection limit.
Post P' Cleaning Samples - There were two air samples and four wipe samples collected
after the first cleaning. All of the samples were below the detection limit, except for one air
sample that was slightly above the detection limit. Since all of the samples were below or
near the detection limits after the first cleaning, no additional samples were collected for
tridymite.
MMVF
Before Cleaning Samples - There were three pre-cleaning wipe samples collected. All three
samples were above the detection limit.
Post J" Cleaning Samples - There were three air samples and five wipe samples collected
after the first cleaning. The results for the three air samples indicate that MMVF was present
with two samples being above the numeric criterion of 10 S/L. The third was below the
numeric criterion. The results of the five wipe samples indicate that MMVF was still present
after the first cleaning at concentrations similar to or higher than the pre-cleaning samples.
There is not a numeric criterion for MMVF in settled dust; however, since two of the air
samples were above the numeric criterion, additional air samples were collected for MMVF.
Post 2"^ Cleaning - There were five air samples collected after the third cleaning. The results
indicate that the two of the five samples were above the numeric criterion. Due to this
situation, additional air samples were collected after the third cleaning.
Post 3''‘‘ Cleaning - There were two air samples collected after the second cleaning. The
results indicate that both samples were below the numeric criterion and both were reported as
being below the detection limit. This indicates that the addition of the AFDs during cleaning
may have aided in the reduction of MMVF in the air.
78
CITY_21MC100_004205034
NYC-WTC_000276730