Dioxin
Before Cleaning Samples - There were three pre-cleaning wipe samples collected and
analyzed for dioxin. The results indicate that there was dioxin present; however, the TEQ
concentration for each sample was below the numeric criterion of 4 ng/m^.
Post Cleaning Samples - There were four post-cleaning wipe samples collected and
analyzed for dioxin. The results indicate that the TEQ concentrations for each sample were
below the criterion of 4 ng/nr and found at lower concentrations than the pre-cleaning
samples.
Gypsum
Before Cleaning Samples - There were three pre-cleaning wipe samples collected. The
results indicate gypsum was not detected above the detection limit of 80 mg/m’.
Post J" Cleaning Samples - There were two air samples and four wipe samples collected after
the first cleaning. The results indicate that gypsum was not detected above the detection limit
for the air samples and not detected above the detection limit for wipe samples. One of the
four wipe samples was not analyzed because filter material was not available.
Lead
Before Cleaning Samples - There were four micro vacuum samples and three wipe samples
collected. The results indicate that all four micro vacuum samples exceeded the comparison
value and two of the three wipe samples exceeded the primary numeric criteria of 25 gg/ft^.
The third wipe sample was below the detection limit. The micro vacuum samples ranged in
concentration from 69.8 gg/fF to 83.7 ggTlg and the wipe samples ranged from non-detect to
181 gg/fV.
Post Cleaning Samples - There were two air samples, three micro vacuum samples, and
four wipe samples collected after the first cleaning. The two air samples were below the
primary numeric criterion of 1 14g/ni\ The results of the micro vacuum and wipe samples
show that all samples met the comparison value or numeric criterion for lead after the first
cleaning; however, three of the four wipe samples were qualified as rejected due to field
blank contamination, and one wipe sample was not analyzed due to not being received at the
laboratory.
Post 2''‘‘ Cleaning Samples - While the study was underway, there was a revision from a
background numeric criterion for lead in air of 0.1 gg/m^ to a health-based numeric criterion
for lead in air of 1.0 iig/m\ The initial results were compared to the background numeric
criterion which resulted in a decision to recline the dwelling and resample for lead in air.
This also occurred in four other units and although these units were cleaned a second time
and Post 2*** cleaning samples collected, the revised lead in air criterion actually negated the
need for the second cleaning and sampling events. There was one air sample collected and