air asbestos results after the second cleaning were at lower concentrations than the pre
cleaning samples and the samples collected after the first cleaning. This indicates that the
cleaning techniques used were efficient at removing asbestos to levels that were below
detection limits and below the primary and secondary numeric criteria.
Dioxin
Before Cleaning Samples - There were four pre-cleaning wipe samples collected and
analyzed for dioxin. The results indicate that there was dioxin present; however, the TEQ
concentrations for each sample were well below the primary numeric criterion of 4 ng/mv
Post J"' Cleaning Samples - There were four post-cleaning wipe samples collected and
analyzed for dioxin. The results indicate that the concentrations of dioxin detected were
similar to the pre-cleaning samples and the TEQ concentrations for each sample were well
below the primary numeric criterion of 4 ng/nr. Since the dioxin samples were below the
numeric criterion for all of the samples collected, there were no additional dioxin samples
collected.
Gypsum
Before Cleaning Samples - There were four pre-cleaning wipe samples collected. The results
indicate that gypsum was not detected.
Post P' Cleaning Samples - There were two air samples and four wipe samples collected
after the first cleaning. The results indicate that gypsum was not detected in any sample.
Since gypsum was below the detection limits for all of the samples collected, there were no
additional gypsum samples collected.
Lead
Before Cleaning Samples - There were three micro vacuum samples and four wipe samples
collected. The results indicate that all three micro vacuum samples were below the detection
limit and at concentrations below the comparison value of 25 pg/ft^ Two of the four wipe
samples had detectable concentrations of lead; however, they were below the primary
numeric criterion of 25 pg/f?. The third sample was below the detection limit and the fourth
sample was lost at the laboratory and was not analyzed.
Post Cleaning Samples - There were two air samples, three micro vacuum samples and
four wipe samples collected after the first cleaning. The two air samples were below the
primary numeric criterion of 1 pg/m\ All tliree micro vacuum samples and one of the four
wipe samples were below the detection limit. Two wipe samples were below the numeric
criterion and the fourth wipe sample was above the primary numeric criterion. Due to the
one lead sample being above the numeric criterion, as well as the asbestos samples that
exceeded the numeric criterion, this unit was cleaned a second time.