TEM PCMe. The PCM results indicate that all three samples were below the
secondary numeric criterion of 0.01 f/cc. The TEM AHERA results indicate that two
of the samples could not be analyzed due to overloading of particulate material. The
remaining sample was below secondary numeric criterion of 0.0022 S/cc. The TEM
PCMe results indicate that two of the samples could not be analyzed due to
overloading of particulate material. The remaining sample was below primary
numeric criterion of 0.0009 S/cc.
The results of the seven micro vacuum samples indicate that asbestos was present at
concentrations lower than those observed before cleaning.
The results of the wipe samples indicate that asbestos was present in all four samples
at higher concentrations than those observed before cleaning.
Post J" Cleaning Samples, Test 4B - Post-cleaning wipe and air samples were
collected for asbestos. Three air samples were analyzed using PCM, TEM AHERA,
and TEM PCMe. The PCM results indicate that two samples could not be analyzed
due to overloading of particulate material and one sample was below the secondary
numeric criterion of 0.01 f/cc. The TEM AHERA and TEM PCMe analyses could
not be analyzed due to overloading of particulate matter.
The results of the four wipe samples indicate that asbestos was present in three of the
four samples at higher concentrations than those observed before cleaning, but similar
to the post 4A samples. One sample was recorded as below the detection limit;
however, the detection limit was greater than normal due to the presence of
particulate material.
Post P' Cleaning Samples, Test 4C - Post-cleaning air and micro vacuum samples
were collected for asbestos. Five air samples were analyzed using PCM, TEM
AHERA, and TEM PCMe. The PCM results indicate that all five samples were
below the secondary numeric criterion of 0.01 f/cc. The TEM AHERA results
indicate that all five samples were below the secondary numeric criterion of 0.022
S/cc. The TEM PCMe results indicate that all five samples were above the primary
numeric criterion of 0.0009 S/cc.
The results of the seven micro vacuum samples indicate that asbestos was present in
concentrations above the detection level in four of the seven samples. However, post
cleanup sample concentrations were lower than those observed before cleaning and
after 4A cleaning.
Post P' Cleaning Samples, Test 4D - Post-cleaning air samples were collected for
asbestos. Three air samples were analyzed using PCM, TEM AHERA, and TEM
106
CITY_21MC100_0 04205062
NYC-WTC_000276758