Commercial Unit; Retail Mattress Store - This is a 968 sq. ft. open space facing the World
Trade Center site. All front windows were blown-in and excessive amounts of dust were
present on all horizontal surfaces. Floor areas were covered with wall to wall carpeting and
approximately 25 display mattresses and box springs were present. Ceiling tiles, mattresses,
office equipment and flexible ventilation ducts were removed and disposed prior to cleaning.
The space above the suspended ceiling exhibited the same characteristics as in the
Chiropractors office.
Cleaning Method - This unit was subject to separate tests to evaluate 5 different
cleaning techniques as described below:
Test 4A; Industrial HEPA filtered vacuums and AFD.
Test 4B: Wet wipe all walls.
Test 4C: Hot water carpet shampoo.
Test 4D: A/C Duct Cleaning
Test 4E: Cleaning of vinyl floor tile and window ledge wet wipe using
water only.
Numeric Criteria - This unit met the numeric criteria listed in Table 1 for each
compound after being cleaned once for each of the five different cleaning techniques.
Supplemental Sampling Activities - Prior to initiating pre-cleanup sampling activities
as described below, EPA collected a bulk composite sample from the Mattress Store.
The analytical data obtained from the bulk composite was utilized in identifying
COPC concentrations present in settled dust, detennining the applicability of
regulatory standards, and identifying potential health and safety concerns. The
Mattress Store was selected, based upon visual observation, as being representative of
a “worst case scenario” for the various units in the Confinnation Cleaning Study
building.
Asbestos
Before cleaning samples - Pre-cleaning air, micro vacuum, and wipe samples were
collected for asbestos. The air samples were analyzed for PCM and TEM PCMe. The
PCM results indicate that two of the samples were above the secondary numeric
criterion of 0.01 f/cc and two samples were below this value. The TEM PCMe results
indicate that two of the samples could not be analyzed due to overloading of
particulate material. The remaining two samples were below the detection limit and
below the primary numeric criterion of 0.0009 S/cc. All seven of the micro vacuum
samples and all three of the wipe samples detected chrysotile.
Post P’ Cleaning Samples, Test 4A - Post-cleaning air, micro vacuum, and wipe were
collected for asbestos. The air samples were analyzed for PCM, TEM AHERA, and