NYC 9/11 Public Portal Document

____ stellpk TONpeerENT 3se884e NO.26a 504

Hygienetics® Environmental Hygiera'aCb Environme'iial Services, Ine 1 West 343, Sueai Phons, is 12) 244-34^3 7th Poor fas; <212) 244-8305 Now SMt. NV 10001 SepteiTibeT 16. 2001

Mr. Victor Purpura Building Manager Stellar Management Two Rector Su'cci New York, NY 10006

Re: Report of Air Sampling Results Two Rector Street -Floors 4-8, IS, 16,18-23 and 27

Dear Mr. Purpu'a:

Ah requested, Hygicnctica Envircrimsnul Services, lac (Hygieissticsl conducted ainbicni eir sampling at the captioned aieas. This air sampliug was conducted on September 13 - 21,2001. I I

Methodology Air monitoring was performed by setting up a sampling train at each sampling location Each train consisted of a high volume air sampling pump, which was calibrated to collect air in accordance with the appropriate sampling methodology (NTOSH 7400 Method for airborne fibers), attached to 0 45 micTOTneter pore size, 25 millimeter diameter mixed cellulose ester membrane filter cassettes with tygon tubing. Open faced cassettes were utilized fq- toe air sampling-

Area air samples were collected at representative interior spaces on each of the referenced foots at Two Rector Street. In addition, field blank samples were also submitted to ths analytical laboratory, for quality controMquaHty assurance (QA/QC) purposes. A total of 74 samples were sybminsd for analysis by Scienpfic Laboraiones, Inc. a New York State Depcrimer.i of Hcaltit (ELAP) Approved laboratory.

On-site pump calibration was performed wnh a lugh-flow roiameter, at die sian and completion of each sample collection penad, to ensure an accurate volumetric reading. The rotameter’s calibration was confirmed prior to its use on-sits, utilizing a Mini Buck Model M-30 bubble calibrator, a primary calibration standard

SampiC. Deca and piscusaior'

Opitcal Phase Contrast Microscope Analysis: Please refer to copies of the attached analytical laboratory's report for the results of the sampling conducted. In summary, toe levels of measured airborne fibers present during the sampling period were relatively low, and did not approach or exceed any applicable, enforceable industnal exposure limits as set by governmental agencies

A: the present time, there arc no nomndustnal indoor ait quality standards, or permissible exposure iimita for airborne asbestos However, a generally atccpicd aireuroc fiber concentration for “Clean Air" subsequent to asbestos ahatement activities in ccmmercial buildings in New York City is 0 01

CITY_21MC100_0 06263409 NYC-WTC_000268390

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000268390Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →