September 26, 2001
Mr. Victor Purpura
Building Manager
Stellar Management
Two Rector Street
New York, NY 10006
Re: Report of Air Sampling Results
Two Rector Street -Floors PI.I._._._._._._._._._._._._
Dear Mr. Purpura:
As requested, Hygienetics Environmental Services, Inc. (Hygienetics) conducted ambient air
sampling at the captioned areas. This air sampling was conducted on September 19 - 21, 2001.
Methodology:
Air monitoring was performed by setting up a sampling train at each sampling location. Each train
consisted of a high volume air sampling pump, which was calibrated to collect air in accordance
with the appropriate sampling methodology (NIOSH 7400 Method for airborne fibers), attached to
0.45 micrometer pore size, 25 millimeter diameter mixed cellulose ester membrane filter cassettes
with tygon tubing. Open faced cassettes were utilized for the air sampling.
Area air samples were collected at representative interior spaces on each of the referenced floors at
Two Rector Street. In addition, field blank samples were also submitted to the analytical laboratory,
for quality control/quality assurance (QA/QC) purposes. A total of 74 samples were submitted for
analysis by Scientific Laboratories, Inc. a New York State Department of Health (ELAP) Approved
laboratory.
On-site pump calibration was performed with a high-flow rotameter, at the start and completion of
each sample collection period, to ensure an accurate volumetric reading. The rotameter's calibration
was confirmed prior to its use on-site, utilizing a Mini Buck Model M-30 bubble calibrator, a
primary calibration standard.
Sample Data and Discussion
Optical Phase Contrast Microscope Analysis:
Please refer to copies of the attached analytical laboratory's report for the results of the sampling
conducted. In summary, the levels of measured airborne fibers present during the sampling period
were relatively low, and did not approach or exceed any applicable, enforceable industrial exposure
limits as set by governmental agencies.
At the present time, there are no non-industrial indoor air quality standards, or permissible exposure
limits for airborne asbestos. However, a generally accepted airborne fiber concentration for "Clean
Air" subsequent to asbestos abatement activities in commercial buildings in New York City is 0.01