Mr. Bernard P. Orlan - May 1, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Proiect No. 15-19125-0290 RI AL- TIM I E NVIRONMENTAL MEASUREMENTS

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are descnbed below.

Temperature

Indoor dry bulb temperature measurements ranged from 66.5 °F to 77.9 °F. Ninety-eight (98) of the indoor measurements for temperature were below and thirty (30) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season . The outdoor temperature ranged from 55.6 to 66.0 °F.

Relative Humidity

The relative humidity indoors ranged from 25.1 percent to 36.3 percent. Sixty-three (63) of the indoor measurements for relative humidity were below and sixty-five (65) measurements were within the ASHRAh-rccommcnded range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 24.3 to 36.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 500 ppm to 1171 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 499 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1199 ppm (background level -I- 700 ppm). The highest measurement (1171 ppm) was collected in the Gymnasium at 3:10 PM with 0 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

CarbonMonoHde Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from Ippm to 4ppm.

Rexpirahle Particuiates (PM2_§)

Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 69 pg/m^ with an average 9 pg/m^- One of the indoor and eleven (11) of the outdoor measurements for PM2,5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter Two (2) of the indoor measurements and all twelve (12) of the outdoor measurements were above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 52 ng m3 to 158 pg/m^ with an average of 84 pg/m^.

CONFIDENTIAL, CITY_21MC100_003464116 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_00026021 1

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260211Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000399222

Indoor air quality measurements at the High School for Leadership & [name]; May 2002.

Similar indexed content

NYC-WTC_000180220

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in May 2002.

Similar indexed content

Compare copies and versions →