NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan - May 1, 2002
Indoor Air Quality Assessment Page 3
H.S. for Leadership & Public Service (M894) ATC Proiect No. 15-19125-0290
RI AL- TIM I E NVIRONMENTAL MEASUREMENTS
ATC collected one hundred and forty (140) sets of real-time environmental measurements
consisting of one hundred and twenty-eight (128) in the school building and twelve (12)
outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the
Attachment. Readings were collected in the morning and evening. The results are descnbed
below.
Temperature
Indoor dry bulb temperature measurements ranged from 66.5 °F to 77.9 °F. Ninety-eight (98) of
the indoor measurements for temperature were below and thirty (30) were within the range of 73
to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during
the summer season . The outdoor temperature ranged from 55.6 to 66.0 °F.
Relative Humidity
The relative humidity indoors ranged from 25.1 percent to 36.3 percent. Sixty-three (63) of the
indoor measurements for relative humidity were below and sixty-five (65) measurements were
within the ASHRAh-rccommcnded range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity range was 24.3 to 36.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 500 ppm to 1171 ppm. All of the indoor
measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration was 499 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1199 ppm (background level -I- 700 ppm). The highest measurement (1171 ppm) was
collected in the Gymnasium at 3:10 PM with 0 occupants. Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of
available outdoor air. The primary source of CO2 indoors is occupant respiration.
CarbonMonoHde Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged
from Ippm to 4ppm.
Rexpirahle Particuiates (PM2_§)
Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 69 pg/m^ with an
average 9 pg/m^- One of the indoor and eleven (11) of the outdoor measurements for PM2,5
were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5
micrometers or less in aerodynamic diameter Two (2) of the indoor measurements and all
twelve (12) of the outdoor measurements were above the USEPA recommended concentration of
40 pg/m3 for sensitive individuals such as asthmatic people and children. The outdoor respirable
particulate concentrations ranged from 52 ng m3 to 158 pg/m^ with an average of 84 pg/m^.
CONFIDENTIAL, CITY_21MC100_003464116
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_00026021 1
OCR can misread numbers and units. Confirm readings against the page image before using them.