Mr. Bernard P. Ori an May 1,2002
Indoor Air Quality Assessment Page 4
H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOCConcentration
The TVOC’s concentrations were 0 ppm inside the building. These concentrations were below the
AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Ninety-eight (98) of the indoor measurements for temperature were below and thirty (30)
were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by
ASHRAE Standard 55-1992 during the summer season.
3. Sixty-tliree (63) of the indoor measurements for relative humidity were below and sixty-five
(65) measurements were within the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort.
4. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. Levels
above the recommended maximum do not indicate a health risk. Carbon dioxide
measurements are used as an indicator of available outdoor air. The primary source of CO2
indoors is occupant respiration.
5. One (1) the indoor and eleven (11) of the outdoor measurements for PM2.5 were above the
NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers
or less in aerodynamic diameter. Two (2) of the indoor and all twelve (12) of the outdoor
measurements were above the USEPA recommended concentration of 40 pg/m^ for
sensitive individuals such as asthmatic people and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, ext. 290 or
212.
Sincerely,
A TC ASSOCIA TES INC.
Reviewed by'
/
I
Yiannis Efstathiou James R. C^, CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CONFIDENTIAL, CITY_21MC100_003464117
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260212