Mr. Bernard P. Orlan March 5, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadershm & Public Service (M894) ATC ProiectNo. 15-19125-0290
RICAL-TIMJLE NVIRONMENTAL MEASUREMENTS
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:18 A.M. and concluded after 3:51 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 62.1 °F to 73.3.9°F. Seven (7) were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 40.4 °F to 53.8 °F.
Relative Humidity
The relative humidity indoors ranged from 19.4 percent to 42.3 percent. One hundred and twenty-five (125) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Three (3) indoor measurements were within the ASHRAE recommended range. The outdoor relative humidity range was 19.4 to 24.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 364 ppm to 1156 ppm. All of the measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations ranged from 308 ppm to 581 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1281 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Adonoxide Concentration
Carbon monoxide concentrations indoors were 1 - 2 ppm. These concentrations were below the NPAAQS/ASIIR?lE guideline of 9 ppm. The outdoor CO concentrations were 1-3 ppm.
Respirable Particulates (PM2 5)
Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 26 pg/m^ with an average 7 pg/m^- None of the indoor measurements were above the NPA4QS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations ranged from 30 pg/m^ to 85 pg/m^ with an average of 55 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CONFIDENTIAL, CITY_21MC100_0 03463515 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259912
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000370407
ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259914
IAQ field report with conditions and scope of work, Mar 6, 2002
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370411
ATC IAQ measurements conducted March 5, 2002 at the referenced NYC BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370422
Indoor air quality measurements collected March 6, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335550
Indoor air quality measurements collected at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296781
ATC IAQ FIELD REPORT for 90 Trinity Place; measurements collected Apr 16, 2002, project 15-19125-0290.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000215187
Report summarizing indoor air quality measurements collected at a high school location in late February 2002 to assess environmental conditions.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410947
Follow-up IAQ report for the referenced NYC BOE project, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260052
ATC report of IAQ measurements at the referenced school, March 22, 2002, for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370389
ATC Associates report of IAQ measurements at High School for Leadership & STEAM, 90 Trinity Place, Mar 1, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410951
BOE-requested IAQ measurements at H.S. Leadership, June 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410943
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000370407
ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370389
ATC Associates report of IAQ measurements at High School for Leadership & STEAM, 90 Trinity Place, Mar 1, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397729
ATC IAQ report for PS 234M; summarizes June 25, 2002 measurements.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259892
IAQ measurements at High School for Leadership & [name], Mar 1, 2002
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000212729
Cover letter and report from ATC Associates detailing indoor air quality measurements collected at PS 234M on June 5, 2002, for the New York City Board of Education.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397591
ATC IAQ measurements at PS 234M to determine maintenance of acceptable indoor air quality.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.
Similar indexed content
IAQ field report with conditions and scope of work, Mar 6, 2002
Similar indexed content
ATC IAQ measurements conducted March 5, 2002 at the referenced NYC BOE school.
Similar indexed content
Indoor air quality measurements collected March 6, 2002 at the referenced school.
Similar indexed content
Indoor air quality measurements collected at the referenced school.
Similar indexed content