Mr. Bernard P Orlan March 5, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (MS94) ATC Proiect No. 15-19125-0290

TP'OC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guidelme for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building v/as occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particles, CO2, CO and TVOCs were below applicable standards and guidelines. 2. One hundred and twenty-five (125) indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Three (3) indoor measurements were within the ASHRAE recommended range. 3. Seven (7) indoor measurements for temperature were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).

It IS our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 336 or 212.

Sincerely, Reviewed by: .4 TC ASSOCIA TES INC.

James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CONFIDENTIAL, CITY_21MC100_0 03463516 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259913

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259913Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370407

ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.

Similar indexed content

NYC-WTC_000259914

IAQ field report with conditions and scope of work, Mar 6, 2002

Similar indexed content

NYC-WTC_000370411

ATC IAQ measurements conducted March 5, 2002 at the referenced NYC BOE school.

Similar indexed content

NYC-WTC_000370422

Indoor air quality measurements collected March 6, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000335550

Indoor air quality measurements collected at the referenced school.

Similar indexed content

Compare copies and versions →