Mr. Bernard P. Orlan May 3,2002
Indoor Air Quality Assessment Page 3
H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements
consisting of one hundred and twenty-eight (128) in the school building and twelve (12)
outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the
Attachment. Readings were collected in the morning and evening. The results are described
below.
Temperature
Indoor dry bulb temperature measurements ranged from 64.6 °F to 76.3 °F. Eighty (80) of the
indoor measurements for temperature were below and forty-eight (48) were within the range of
73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992
during the summer season . The outdoor temperature ranged from 59.8 to 69.3 °F.
Relative Humidity
The relative humidity indoors ranged from 42.4 percent to 56.7 percent. All of the indoor
measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity range was 43.0 to 59.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 496 ppm to 1589 ppm. One (1) of the indoor
measurements for CO2 Was above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration was 567 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1267 ppm (background level + 700 ppm). The highest measurement (1589 ppm) was
collected in the Gymnasium around 10:55 A.M. with 13 occupants. Levels above the
recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as
an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
CarhonJ^noxideConcentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged
from Ippm to 4ppm.
Respirable Particulates (PM2,s)
Respirable particulate concentrations* indoors ranged between 1 gg/m^ to 55 Mg/m^ with an
average 19 pg/m^- Seven (7) of the outdoor measurements for PM2,5 were above the NPAAQS
of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter Five (5) of the indoor measurements and eleven (11) of the outdoor
measurements were above the USEPA recommended concentration of 40 pg/ra^ for sensitive
individuals such as asthmatic people and children. The outdoor respirable particulate
concentrations ranged from 39 pg/m^ to 158 pg/m^ with an average of 94 pg/m^.