Mr. Bernard P. Orlan April 18, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (MSQdl ATC Project No. 15-19125-0290 Real-Time Envtronmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty eighteen (128) in the school building and twelve (12) outdoors. All fowteen floors of the school were surveyed. Field data sheets are found m the Attachment. Readings began in the morning and concluded in the afternoon. The results are described below.
Temperature
1. Indoor dry bulb temperature measurements ranged from 86.2°F to 90.9 °F. All of the indoor measurements for temperature were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature range was 84.9 °F to 86.4 °F.
Relative Humidity
The relative humidity indoors ranged from 39.9 percent to 48.6 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 48.6 to 51 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 517 ppm to 1201 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentration was 726 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1426 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
C^’bonJ^dono^d^Concentration
Carbon monoxide concentrations indoors ranged from 2 ppm to 3 ppm. These concentrations were below the NTAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations are 2 ppm to 3 ppm.
Respirable Particulates (PM2,§)
Respirable particulate concentrations* indoors ranged between 21 pg/m^ to 51 pg/m^ with an average 37 pg/m^. All of the indoor and outdoor measurements for PM2.5 were below the NP AAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and seventy six (76) measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 42 pg/m^ to 47 pg/m^ with an average of 45 pg/m-.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CONFIDENTIAL, CITY_21MC100_003463947 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260106
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000410947
Follow-up IAQ report for the referenced NYC BOE project, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410951
BOE-requested IAQ measurements at H.S. Leadership, June 24, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410943
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394783
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394768
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394787
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292020
ATC IAQ measurements collected June 24, 2002 for the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296785
ATC IAQ measurements at 90 Trinity Place; report dated Apr 17, 2002; project 15-19125-0290.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296781
ATC IAQ FIELD REPORT for 90 Trinity Place; measurements collected Apr 16, 2002, project 15-19125-0290.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410955
ATC letterhead memo re IAQ measurements for H.S. Leadership, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410959
ATC memo reporting IAQ measurements for school in NYC BOE program, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410939
Documentation of accreditation scope for bulk asbestos analysis at ATC lab.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000410959
ATC memo reporting IAQ measurements for school in NYC BOE program, June 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410955
ATC letterhead memo re IAQ measurements for H.S. Leadership, June 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410951
BOE-requested IAQ measurements at H.S. Leadership, June 24, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260281
May 7, 2002 IAQ measurements; BOE requested testing.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291705
Indoor air quality report for High School for Leadership & [name], May 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410943
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Follow-up IAQ report for the referenced NYC BOE project, June 2002.
Similar indexed content
BOE-requested IAQ measurements at H.S. Leadership, June 24, 2002.
Similar indexed content
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
Similar indexed content
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content