Mr. Bernard P. Orlan June 26, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 78.1 to 82.2 °F. One hundred and four (104) of the indoor measurements were above the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 82.6 to 89.2 °F.
Relative Humidity
The relative humidity indoors ranged from 40.9 percent to 56.2 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 40.5 to 51.6 percent.
CqrbpnDioxideConcentration
Carbon dioxide concentrations indoors ranged from 515 ppm to 754 ppm. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 589 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1289 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
CqrbonMonwddeCon^ntration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.
Respirable Particulates (PM2 ^)
Respirable particulate concentrations* indoors ranged between 9 pg/m^ to 14 pg/m^ with an average 10 pg/m^- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 49 pg/m^ to 126 pg/m^ with an average of 71 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CONFIDENTIAL, CITY_21MC100_001898201 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 NYC-WTC_000410957
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000410959
ATC memo reporting IAQ measurements for school in NYC BOE program, June 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410951
BOE-requested IAQ measurements at H.S. Leadership, June 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188389
Memo reporting indoor air quality measurements collected at a school on June 25, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292024
ATC IAQ measurements collected June 26, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410943
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410947
Follow-up IAQ report for the referenced NYC BOE project, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335305
ATC reports IAQ measurements conducted June 25, 2002 at the referenced NYC school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000380933
Indoor air quality measurements at H.S. for Leadership & [name] as part of BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292012
ATC IAQ measurements collected June 20-21, 2002 for the referenced BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292020
ATC IAQ measurements collected June 24, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296781
ATC IAQ FIELD REPORT for 90 Trinity Place; measurements collected Apr 16, 2002, project 15-19125-0290.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335293
Indoor air quality measurements at M894; June 21, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000410959
ATC memo reporting IAQ measurements for school in NYC BOE program, June 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410951
BOE-requested IAQ measurements at H.S. Leadership, June 24, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410943
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410935
ISO/IEC quality systems-related material associated with project records.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291988
ATC IAQ measurements collected June 11, 2002 for the referenced BOE school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410947
Follow-up IAQ report for the referenced NYC BOE project, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC memo reporting IAQ measurements for school in NYC BOE program, June 2002.
Similar indexed content
BOE-requested IAQ measurements at H.S. Leadership, June 24, 2002.
Similar indexed content
NYC-WTC_000188389
Memo reporting indoor air quality measurements collected at a school on June 25, 2002.
Similar indexed content
ATC IAQ measurements collected June 26, 2002 for the referenced school.
Similar indexed content
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
Similar indexed content