Mr. Bernard P. Orlan June 18, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290

Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 72.2 to 81.3 °F. Five (5) of the indoor measurements for temperature were below and four (4) of the measurements were above the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature ranged from 76.8 to 83.1 °F.

Relative Humidity

The relative humidity indoors ranged from 41.6 percent to 48.9 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 39.4 to 45.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 570 ppm to 1126 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the backgroimd level. The outdoor (background) CO2 concentration was 682 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1382 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

CarbonMonoxideConcentratim

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 4 gg/m^ to 18 pg/m^ with an average 8 pg/m^- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 42 pg/m^ to 83 pg/m^ wiSi an average of 60 pg/m^.

CONFIDENTIAL, CITY_21MC100_001898106 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 NYC-WTC_000410937

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000410937Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000410919

Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.

Similar indexed content

NYC-WTC_000410915

IAQ measurements at 90 Trinity Place; BOE requested assessment of air quality.

Similar indexed content

NYC-WTC_000292004

ATC IAQ measurements collected June 17, 2002 for the referenced school.

Similar indexed content

NYC-WTC_000410931

IWQ measurements and narrative for H.S. Leadership project, June 2002.

Similar indexed content

Compare copies and versions →