Mr. Bernard P. Orlan June 12, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 74.5 to 85.8 °F. Thirteen (13) of the indoor measurements for temperature were above the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 75.^ to 87.8 °F.
RelgtiyeHumidify
The relative humidity indoors ranged from 41.1 percent to 59.1 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 58.2 to 65.6 percent.
CgrbonDioxideCpnc^tratipn
Carbon dioxide concentrations indoors ranged from 563 ppm to 1410 ppm. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 523 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1223 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.
Respirable Particulates (PM2_s)
Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 37 pg/m^ with an average 20 pg/m^- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 128 pg/m3 to 280 pg/m^ ■^ith an average of 139 pg/m^.
CITY_21MC100_003079746
NYC-WTC_000291990
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000292004
ATC IAQ measurements collected June 17, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399528
June 10, 2002 IAQ measurements update letter to BOE.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399516
June 5, 2002 IAQ measurement report for Leadership & [name] at 90 Trinity Place.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399504
Correspondence about IAQ measurements at the school, May 30, 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291976
ATC IAQ measurements conducted June 4, 2002 for BOE at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399496
Indoor air quality report for the referenced NYC BOE school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291984
ATC IAQ measurements collected June 10, 2002 for the school per BOE request.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188385
Memo reporting indoor air quality measurements collected at a school on June 7, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399512
June 4, 2002 IAQ measurements update letter to BOE for the school at 90 Trinity Place.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410919
Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291942
Indoor air quality measurements at HS Leadership, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000399512
June 4, 2002 IAQ measurements update letter to BOE for the school at 90 Trinity Place.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399348
IAQ measurements collected May 14, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399402
Indoor air quality measurements collected May 17, 2002, for the High School for Leadership & [name].
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291805
Report of lAQ measurements for HS Leadership at 90 Trinity Place, May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188377
Memo reporting indoor air quality measurements collected at a school on May 17, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291964
ATC report detailing IAQ measurements at High School for Leadership & [name], Trinity Place, May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC IAQ measurements collected June 17, 2002 for the referenced school.
Similar indexed content
NYC-WTC_000399528
June 10, 2002 IAQ measurements update letter to BOE.
Similar indexed content
NYC-WTC_000399516
June 5, 2002 IAQ measurement report for Leadership & [name] at 90 Trinity Place.
Similar indexed content
NYC-WTC_000399504
Correspondence about IAQ measurements at the school, May 30, 2002.
Similar indexed content
ATC IAQ measurements conducted June 4, 2002 for BOE at the referenced school.
Similar indexed content