, Mr. Bernard P. Orlan May 7, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmewtal Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 70.1 °F to 85.1 °F. One hundred and four (104) of the indoor measurements for temperature were below and one (1) was above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the summer season . The outdoor temperature ranged from 71.1 to 72.3 °F.
Relative Humidity
The relative humidity indoors ranged from 43.9 percent to 50.6 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 45.4 to 49.3 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 410 ppm to 1260 ppm. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 471 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1171 ppm (background level + 700 ppm). The highest measurement (1260 ppm) was collected in room # 905 around 1:10 P.M. with 33 occupants. Levels'above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also Ippm for all readings.
Respirable Particulates (PM2 H
Respirable particulate concentrations* indoors ranged between 19 pg/m^ to 39 pg/m^ with an average 28 pg/m^- All the indoor measurements for PM2.5 were within the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 26 pg/m^ to 46 pg/m^ with an average of 34 pg/m^.
CONFIDENTIAL, CITY_21MC100_003464188 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260283
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000260419
ATC provides indoor air quality measurements collected May 20, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399272
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399254
Indoor air quality report dated May 7, 2002 for High School project; ATC.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410931
IWQ measurements and narrative for H.S. Leadership project, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260505
ATC IAQ measurement report for High School for Leadership & [name], May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410939
Documentation of accreditation scope for bulk asbestos analysis at ATC lab.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180220
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260451
Indoor air quality measurements taken May 22, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296912
IAQ measurements at the referenced school in Apr 2002, part of a program to determine if IAQ is maintained.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410919
Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260347
ATC provides IAQ report for May 14, 2002 measurements at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188377
Memo reporting indoor air quality measurements collected at a school on May 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000399272
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291705
Indoor air quality report for High School for Leadership & [name], May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260347
ATC provides IAQ report for May 14, 2002 measurements at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291723
Indoor air quality measurements report for HS Leadership & [name], May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399290
Indoor air quality measurements collected May 8, 2002, at the referenced school for BOE evaluation.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410931
IWQ measurements and narrative for H.S. Leadership project, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC provides indoor air quality measurements collected May 20, 2002.
Similar indexed content
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
Similar indexed content
Indoor air quality report dated May 7, 2002 for High School project; ATC.
Similar indexed content
IWQ measurements and narrative for H.S. Leadership project, June 2002.
Similar indexed content
NYC-WTC_000260505
ATC IAQ measurement report for High School for Leadership & [name], May 2002.
Similar indexed content