Indoor air quality report, HS Leadership, Apr 2002

Machine-extracted title · confidence 32%

ATC IAQ measurements collected April 12, 2002 at the referenced school for NYC BOE.

NYC-WTC_000260096–000260099
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 15,2002 Indoor Air Quality' Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 RiiAL-TiME Environmental Measurements

ATC collected one hundred and twenty three (123) sets of real-time environmental measurements consisting of one hundred and fifteen (115) m the school building and eight (8) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8.00 A.M. and concluded after 6:20 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 67.2 °F to 78.4 °F. Seven indoor measurements were above, and one (1) measurement was bellow, seven (7) measurements were above, and one hundred seven (107) indoor measurements for temperature were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 52.6 °F to 77.2 °F.

Re!.atiy^Humui^

The relative humidity indoors ranged from 27.0 percent to 48.6 percent. Eleven (11) of the indoor measurements for relative humidity were below and one hundred and four (104) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant cornfort. The outdoor relative humidity range was 27.1 to 37.2 percent.

Carbon DioxideOmcentratipn

Carbon dioxidf^ ccmcentrations indoors ranged from 357 ppm to 961 ppm. One hundred and fifteen (115) readings of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentration was 684 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1384 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO? indoors is occupant respiration.

QrrbonMonc^de Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NP AAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm- 3 ppm.

Respirable Pariiculates (PM2j)

Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 49 pg/m^ with an average 12 pg/m^- All of the indoor measurements for PM2,5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and three (3) Indoor Measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children, the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 12 pg/m^ to 51 pg/m^

CONFIDENTIAL, CITY_21MC1OO_OO3463912

SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260098

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260098Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000260177

April 29, 2002; cover about IAQ measurements at the school.

Similar indexed content

NYC-WTC_000394752

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

Compare copies and versions →