Mr. Bernard P. Orlan April 11,2002 Indoor Air Quality Assessment Page 3 H.S. for Leadershiii & Public Service (M894) ATC Project No. 15-19125-0290 REAL-TlMi E?J\ niONMENTAL MEASUREMENTS
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 11:17 A.M. and concluded after 17:46 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 64.4 °F to 75.2 °F. One (1) indoor measurements for temperature was above, One (1) indoor measurements for temperature was below and one hundred twenty six (126) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 53.6 °F to 63.9 °F.
Relqtiy^umj^ity
The relative humiclity indoors ranged from 28.8 percent to 49.4 percent. Five (5) of the indoor measurements for relative humidity were below and one hundred twenty three (123) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Idle outdoor relative humidity range was 29.5 to 41.1 percent.
CarbpnDioxide Concentration
Carbon dioxide concentrations indoors ranged from 485 ppm to 1639 ppm. One hundred and twenty six (126) readings of the indoor measurements for CO2 were below the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 488 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1188 ppm (background level + 700 ppm). The highest levels ' 639. 1442 were detected m Gymnasium and 12^" floor hallway with forty three (43) occupants in Gymnasium.Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of (302 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm- 5 ppm.
Respirable Particulates (PM2 j)
Respirable paniculate concentrations* indoors ranged between 5 pg/m^ to 24 pg/m^ with an average 11 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 16 pg/m^ to 51 pg/m^ with an average of 34 pg/m3. None of the
CONFIDENTIAL, CITY_21MC100_003463876 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260090
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000394752
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260177
April 29, 2002; cover about IAQ measurements at the school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260096
ATC IAQ measurements collected April 12, 2002 at the referenced school for NYC BOE.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260136
ATC IAQ measurements collected April 23, 2002 at the referenced school for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394813
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296816
ATC IAQ measurements report for 90 Trinity Place, Apr 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259960
IAQ measurements collected Mar 12, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260100
ATC IAQ measurements collected April 15, 2002 at the referenced school for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370492
Indoor air quality measurements collected March 12, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260092
ATC IAQ report for 90 Trinity Place, measurements collected April 11, 2002, BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179972
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 8, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260227
May 2, 2002 IAQ measurements requested by BOE for school.
14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000260177
April 29, 2002; cover about IAQ measurements at the school.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260096
ATC IAQ measurements collected April 12, 2002 at the referenced school for NYC BOE.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394752
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179972
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 8, 2002.
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370534
Indoor air quality measurements collected March 21, 2002 at the referenced school.
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260033
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content
April 29, 2002; cover about IAQ measurements at the school.
Similar indexed content
NYC-WTC_000260096
ATC IAQ measurements collected April 12, 2002 at the referenced school for NYC BOE.
Similar indexed content
NYC-WTC_000260136
ATC IAQ measurements collected April 23, 2002 at the referenced school for BOE.
Similar indexed content
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content