Mr. Bernard P. Orlan April 29, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadershiti & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time En5tponmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperaiiire

Indoor dry bulb temperature measurements ranged from 70.0 °F to 79.7 °F. Fifty two (52) of the indoor measurements for temperature were below, two (2) measurements were above and seventy four (74) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (summertime conditions). Tfe outdoor temperature ranged from 56.4 to 69.7 °F.

Relative Humidity

The relative humidity indoors ranged from 18.3 percent to 43.4 percent. One hundred eighteen (118) of the indoor measurements for relative humidity' were bellow and ten (10) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 16.2 to 34.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 481 ppm to 1631 ppm. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 575 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1275 ppm (background level + 700 ppm).These two measurements were collected from Basement Gym Lounge (1631ppm), Basement Gym (1419ppm) with twenty five occupants. These measurements were collected at approximately 2:25 PM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of avai lable outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbol MonoHde Concentration

Carbon monoxide concentrations indoors ranged from Oppm to 2ppm These concentrations were below the NPAXQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from Ippm to 4ppm. Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 2 pg/m3 to 23 pg/m^ with an average 8 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All measurements were also below than the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 31pg/m3 to 79 pg/m^ with an average of 53pg,nvL

CONFIDENTIAL, CITY_21MC100_003464080 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260179

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260179Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000394752

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

NYC-WTC_000394813

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

Compare copies and versions →