NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, High School for Leadership & [name], Apr 2002

Machine-extracted title · confidence 36%

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

NYC-WTC_000394752–000394755
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 11, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 11:17 A.M. and concluded after 17:46 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 64.4 °F to 75.2 °F. One (1) indoor measurements for temperature was above, One (1) indoor measurements for temperature was below and one hundred twenty six (126) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 53.6 °F to 63.9 °F.

Relative Humidity

The relative humidity indoors ranged from 28.8 percent to 49.4 percent. Five (5) of the indoor measurements for relative humidity were below and one hundred twenty three (123) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 29.5 to 41.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 485 ppm to 1639 ppm. One hundred and twenty six (126) readings of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 488 ppm. Therefore, the maximum ' acceptable level of CO2 at this location was 1188 ppm (background level + 700 ppm). The highest levels 1639, 1442 were detected in Gymnasium and 12th floor hallway with forty three (43) occupants in Gymnasium.Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The . primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm- 5 ppm.

Respirable Particulates (PM}, 5)

Respirable particulate concentrations* indoors ranged between 5 pg/m^ to 24 pg/m^ with an average 11 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 16 pg/m3 to 51 pg/m3 with an average of 34 pg/m3. None of the

CITY_21MC100_002918546

NYC-WTC_000394754

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000394754Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000394813

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

NYC-WTC_000370492

Indoor air quality measurements collected March 12, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000399204

IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.

Similar indexed content

Compare copies and versions →