NYC 9/11 Public Portal Document
Mr. Bernard P. Orian March T 2002
Indoor Air Quaiin .Assessment Page 3
H.S. for Leadershio & Public Service (M894) ATC Project No. 15-19125-0290
Real-Tim e E nv i ronmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements
consisting of one hundred and twenty-eight (128) in the school building and twelve (12)
outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the
Attachment. Readings began at 11:10 A.M. and concluded after 7:43 P.M. The results are
described below.
Temperature
Indoor dry bulb temperature measurements ranged from 60.9°F to 75.0°F. Ten (10) were below
the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard
55-1992 during the heating season (wintertime conditions). The outdoor temperature range was
42.9°Fto58,7°F.
Relative Humidity
The relative humidity indoors ranged from 18.4 percent to 42.5 percent. Eight (8) measurements
were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All
other relative huiTudity measurements were below the ASRAE recommended range. The
outdoor relative humidity range was 18.4 to 42.5 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 423 ppm to 984 ppm. None of the
measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) COn
concentrations ranged from 267 ppm to 521 ppm. Therefore, the maximum acceptable level of
COy at this location was 1221 ppm (background level + 700 ppm). Levels above the
recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as
an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-2 ppm. These concentrations were below the
NPAAQS/ASHRAEi guideline of 9 ppm. The outdoor CO concentrations were 1-3 ppm.
Respirable Particulates (PM2^ H
Respirable particulate concentrations* indoors ranged betw'een 1 pg/m-’ to 28 pg/mJ with an
average 7 pg/m-’- None of the measurements were above the NPAAQS of 65 pg/m-’ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.
The outdoor respirable particulate concentrations ranged from 18 pg/m-’ to 71 pg/m’ with an
average of 44 pg/m”.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.