Mr. Bernard P. Orlaii March 1,2002
Indoor Air Qualit}' .Assessment Page 2
H.S. for Leadership (S: Public Service (M894) ATC Project No. 15-19125-0290
The assessment was performed consistent with generally' accepted indoor air quality assessment
practices. As with all such assessments, there were inherent limitations created by constraints of
time, operational and work practice variability, variations in indoor air quality parameters and
sampling and analytical accuracy.
The results of the sampling represent conditions found on the dates of the surt'ey and may not
represent conditions found at other times. The information presented in this report should be
used by the BOE as a guide to assess the need for further impro\'ements in current indoor air
quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings,
such as offices and schools. For the real-time data collected, ATC uses the commonly accepted
guidelines citec in the following publications;
Ventilafion for Acceptable Indoor Air Quality (ASHAiE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation.
Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality
will be achieved at .all times.
TABLE 1
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGETLEVEL AGENCY OR
ORGANIZATION
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2)____________ above background level
Carbon Monoxide 9 ppm ASHRAE 62 (adopted from
(CO) USEPA NPAACOS)
Respirable 65 micrograms per cubic meter USEPA NPAAQS
Particulates (PM?,5) of air (pg/m-Q 24-hour average
40 pig/m-’ 24-hour average USEPA - Recommendation for
children / sensitive individuals
Temperature Summer: 73-79°F at 50% RH ASHRAE 55
Winter: 68-75°F at 50% RH
Relative Humidity 30 - 60 % ASHFL^E 55
Total Volatile
Organic Compounds 1 ppm AIHA
(TVOC)
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient-Air Quality Standard
■AIHA = American Industrial Hygiene .Association
CONFIDENTIAL, CITY_21MC100_003463478
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259889