NYC-WTC_000402510
Report of IAQ measurements collected March 18, 2002 at the HS building.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗IAQ measurements collected April 11, 2002 for BOE program.
NYC-WTC_000259180–000259183OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 12, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATCProiectNoM5-19125;0291 Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began atl0:53 A.M. and concluded after 17:57 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 70.5 °F to 76.5 °F. Eleven (11) of the indoor measurements for temperature were above, and seventy seven (77) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 56.3 to 62.2 °F.
Relative Humidity
The relative humidity indoors ranged from 29.6 percent to 40.0 percent. Seven (7) of the indoor measurements for relative humidity were below and eighty one (81) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 28.4 to 35.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 476 ppm to 1104 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentration was 614 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1314 ppm (background level + 700 ppm). Levels above the recommended maximum do no t indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were between 1 to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 2 ppm to 4 ppm.
Respirable Particulates (PM2 §J
Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 13 pg/m^ with an average 5 pg/m^- None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 18 pg/m^ to 82 pg/m-^ with an average of 36 pg/m^. None of the outdoor measurements were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Four (4) of the twelve (12) instantaneous outdoor reading were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.
CONFIDENTIAL, CITY_21MC100_003462230 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259182
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000402510
Report of IAQ measurements collected March 18, 2002 at the HS building.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384222
Indoor air quality measurements collected for the HS of Economics & Finance; BOE involvement.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259153
Indoor air quality measurements collected March 26, 2002 for school.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259141
Indoor air quality measurements collected on March 20, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000254302
Indoor air quality measurements at H.S. Economics & Finance (M833) facility, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259038
Indoor air quality measurements conducted March 7, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259157
ATC notes and observations for IAQ measurements at the school, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259136
Indoor air quality measurements report for the High School of Economics and Finance, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259086
ATC indoor air quality report for the High School of Economics and Finance, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399204
IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259937
IAQ measurements collected Mar 8, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402529
Indoor air quality report for HS Economics & Finance, March 20, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259153
Indoor air quality measurements collected March 26, 2002 for school.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402510
Report of IAQ measurements collected March 18, 2002 at the HS building.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399204
IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.
Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260116
ATC IAQ measurements collected April 19, 2002 for HS Leadership; BOE program.
Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259157
ATC notes and observations for IAQ measurements at the school, March 2002.
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259141
Indoor air quality measurements collected on March 20, 2002 for BOE.
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000402510
Report of IAQ measurements collected March 18, 2002 at the HS building.
Similar indexed content
NYC-WTC_000384222
Indoor air quality measurements collected for the HS of Economics & Finance; BOE involvement.
Similar indexed content
Indoor air quality measurements collected March 26, 2002 for school.
Similar indexed content
Indoor air quality measurements collected on March 20, 2002 for BOE.
Similar indexed content
NYC-WTC_000254302
Indoor air quality measurements at H.S. Economics & Finance (M833) facility, March 2002.
Similar indexed content