IAQ memo, High School of Economics and Finance, Mar 2002

Machine-extracted title · confidence 30%

ATC notes and observations for IAQ measurements at the school, March 2002.

NYC-WTC_000259157–000259160
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 28, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Rea -TiME Environmental Measurements

Arc collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the /dtachment. Readings began at 11:01 A.M. and concluded after 5:27 P.M. The results are desenbed below.

Temperature

Indoor dry bulb temperature measurements ranged from 64.9 °F to 76.7 °F. Five (5) of the indoor measurements for temperature were below, two (2) measurements were above, and eighty-one (81) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime cond tions). The outdoor temperature ranged from 51.2 to 61.4 °F.

Relative Humidity

The lelative humidity indoors ranged from 29.7 percent to 46.7 percent. Two (2) of the indoor measrrements for relative humidity were below and eighty-six (86) were within the ASHRAF recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 32.6 to 51.4 percent.

Carban Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 381 ppm to 894 ppm. All of the indoor measurements for CO2 were below the ASHRAF Standard 62-1999 recommended maximum conctntration of <700 ppm above the background level. The outdoor (background) CO;; concentration was 412 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1112 ppm (background level -r 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carb(>n monoxide concentrations indoors were between 1 to 2 ppm. These concentrations were below the NPiVAQS/ASHRAF guideline of 9 ppm. The outdoor CO concentration ranged from 2 ppm to 4 ppm.

Respi‘-ahle Particulates (PM2^j)

Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 26 pg/m- with an average 5 pg/m^- None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24 - hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concenPation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 21 pg/m^ to 76 pg/m-* with ;,n average of 40 pg/m^. One (1) of the outdoor measurements was above the NPAAQS of 65 pg/m-^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Four (5) of the twelve (12) instantaneous outdoor reading were above the USEF A recommended concentration of 40 pg/m^ for sensitive individuals and children.

CONFIDENTIAL, CITY_21MC100_003462169 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259159

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259159Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259153

Indoor air quality measurements collected March 26, 2002 for school.

Similar indexed content

NYC-WTC_000259086

ATC indoor air quality report for the High School of Economics and Finance, March 2002.

Similar indexed content

NYC-WTC_000259136

Indoor air quality measurements report for the High School of Economics and Finance, March 2002.

Similar indexed content

NYC-WTC_000259141

Indoor air quality measurements collected on March 20, 2002 for BOE.

Similar indexed content

Compare copies and versions →