Mr Bernard P Orlan August 28 2002
Indoor Air Quality Assessment Page 3
JHS 131M_______________________________ ATCProiectNo 15 19125 0346
RealTime Environmental Measurements
ATC collected fifty (50) sets of real time environmental measurements consisting of forty seven
(47) in the school building and three (3) outdoors All floors of the school were surveyed Field
data sheets are found in the Attachment Readings were collected in the morning and evening
The results are described below
Temperature
Indoor dry bulb temperature measurements ranged from 76 9 to 89 3 F Forty (40) of the indoor
measurements were above the range of 73 to79 F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55 1992 during the summer season The outdoor
temperature ranged from 81 8 to 83 5 °F
Relative Humidity
The relative humidity indoors ranged from 41 2 percent to 59 2 percent All of the indoor
measurements for relative humidity were within the ASHRAE recommended range of 30 to 60
percent for occupant comfort The outdoor relative humidity measurements ranged from 50 2 to
50 5 percent
CarbonDioxi^ Concentration
Carbon dioxide concentrations indoors ranged from 419 ppm to 1193 ppm Two (2) of the
indoor measurements for CO2 were above the ASHRAE Standard 62 1999 recommended
maximum concentration of <700 ppm above the background level The outdoor (background)
CO2 concentration was 411 ppm Therefore the maximum acceptable level of CO2 at this
location was 1111 ppm (background level + 700 ppm) The highest reading was measured in the
basement office with 9 occupants at 2 46 PM Carbon dioxide measurements are used as an
indicator of available outdoor air The pnmary source of CO2 indoors is occupant respiration
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm These concentrations
were within the NPAAQS/ASHRAE guideline of 9 ppm The outdoor CO concentrations was 2
ppm for all readings
Respirable Particulates (PM2 3)
Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 78 pg/m^ with an
average 33 pg/m^ Two (2) of the indoor measurements for PM2 5 were above the NPAAQS of
65 pg/m3 24 hour average concentration of particulate matter 2 5 micrometers or less in
aerodynamic diameter Eight (8) of the forty seven (47) instantaneous indoor readings were
above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as
asthmatic people and children The outdoor respirable particulate concentrations ranged from 38
pg/m3 to 39 pg/m^ with an average of 38 pg/m^ All of the outdoor measurements for PM2 5
were below the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5
micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40
pg/m^ for sensitive individuals such as asthmatic people and children