Mr Bernard P Orlan August 28 2002
Indoor Air Quality Assessment Page 2
JHS 131M ATCProiectNo 15 19125 0346
The results of the sampling represent conditions found on the dates of the survey and may not
represent conditions found at other times The information presented in this report should be
used by the DOE as a guide to assess the need for further improvements in current indoor air
quality control activities
EVALUATION CRITERIA
Currently there are no regulatory standards for indoor air quality in non industrial buildings
such as offices and schools For the real time data collected ATC uses the commonly accepted
guidelines cited in the following publications
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62 1999) American Society of
Heating Refrigerating and Air Conditioning Engineers (ASHRAE)
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55 1992)
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993) American
Industrial Hygiene Association (AIHA)
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation
Meeting one some or all of the listed values does not assure that acceptable indoor air quality
will be achieved at all times
TABLE 1
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
[AGENfeYj^J
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2)____________ above background level
Carbon Monoxide 9 ppm ASHRAE 62 (adopted from
ICO)__________ USEPA NPAAQS)
Respirable 65 micrograms per cubic meter USEPA NPAAQS
Particulates (PM2 5) of air (pg/m3) 24 hour a\ erage
40 pg/m^ 24 hour average USEPA - Recommendation for
children / sensitive individuals
Temperature Summer 73 79 F at 50% RH ASHRAE 55
Winter 68 75 F at 50% RH
Relative Humidity 30-60% ASHRAE S5
Total Volatile
Organic Compounds 1 ppm AIHA
(TVOC)
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient Au Quality Standard
AIHA = American Industrial Hygiene Association