Mr Bernard P Orlan August 28 2002
Indoor Air Quality Assessment Page 4
JHS131M ATC Protect No 15 19125 0346
* The measurements made during this assessment were instantaneous readings the NPAAQS is
a 24 hour average
TFOC Concentration
The TVOCs indoor concentrations ranged from 0 1 to 0 2 ppm These concentrations were below
the AIHA guideline for odor control of 1 ppm The outdoor TVOC concentration was 0 ppm
OBSERVATIONS
During this assessment ATC noted the following
• The interior of the building appeared clean and free of dust and debris
• The building was not occupied at the time of the assessment
• No smoke odor was detected in the building
FINDINGS
Based on the real time measurements the following findings are presented
1 Concentrations of CO and TVOCs were within applicable standards and guidelines
2 Forty (40) of the indoor measurements were above the range of 73 to79 °F (at 50 percent
relative humidity) recommended by ASHRAE Standard 55 1992 during the summer season
3 All of the indoor measurements for relative humidity were within the ASHRAE
recommended range of 30 to 60 percent for occupant comfort
4 Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62 1999
recommended maximum concentration of <700 ppm above the background level The
highest reading was measured in the basement office with 9 occupants at 2 46 PM Carbon
dioxide measurements are used as an indicator of available outdoor air The primary source
of CO2 indoors is occupant respiration
5 Two (2) of the indoor measurements for PM2 5 were above the NPAAQS of 65 pg/m^ 24
hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic
diameter Eight (8) of the forty seven (47) instantaneous indoor readings were above the
USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic
people and children All of the outdoor measurements for PM2 5 were below the NPAAQS
of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in
aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for
sensitive individuals such as asthmatic people and children