Mr. Bernard P. Orlan Januar)' 17, 2002
Indoor Air Quality Assessment Page 4
P. S. 89 fManhattanl ATC Project No. 15-19125-0297
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was not occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO2, CO and TVOCs were within applicable
standards and guidelines; '
2. All indoor measurements of relative humidity were below the ASHRAE-reoommended range
of 30 to 60 percent for occupant comfort;
3. Nineteen (19) temperature measurements were above the range of 68 to 75° F (at 50 percent
relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season
(wintertime conditions). These readings were collected from the pt floor.
It is our pleasure to provide these indoor air quality services to the New York City Board of '
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or 212.
Sincerely,
ATC ASSOCIATES INC.
Reviewed by:
Yiannis Efsta^hou James R. Cohn, CIH, CSP
Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CONFIDENTIAL INSURANCE INFORMATION, SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT 2008 CITY_21 MC100_014676344