Mr. Bernard P. Grlan January 17,2002 Indoor Air Quality Assessment Pages P. S. 89 (Manhattan) ATC Project No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected thirty (30) sets of real-time environmental measurements consisting of twenty- three (23) from the 1st floor of the school building and seven (7) outdoors from the playground as per the request of the Parents associations environmental consultant. These results are described below. The field data sheets are found in Attachment 1.

Temperature

Indoor dry bulb temperature measurements ranged from 65.2 °F to 69.7 °F. Nineteen (19) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected from the l^t floor. The outdoor temperature measurements at the playground ranged from.44.0 to 45 .2 °F.

Relative Humidity

The relative humidity indoors ranged from 19.0 percent to 28.1 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 20.0 to 21.0 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 409 ppm to 499 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (backgiound) CO2 concentrations were 420, 435, 430, 435, 435, 440 and 430 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1140 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school building during ATC’s assessment was not occupied.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged between 4 pg/m^ toll pg/m-. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentration ranged from 10 - 13 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CONFIDENTIAL INSURANCE INFORMATION, SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT 2008 CITY_21 MC100_014676343

NYC-WTC_000236984

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000236984Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →