Mr. Bernard P. Orlan January' 17, 2002
Indoor Air Quality Assessment Page 3
P. S. 89 (Manhattan) ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected thirty (30) sets of real-time environmental measurements consisting of twenty-
three (23) from the Pt floor of the school building and seven (7) outdoors from the playground
as per the request of the Parents associations environmental consultant. These results are
described below. The field data sheets are found in Attachment 1.
Temoerature
Indoor dry bulb temperature measurements ranged from 65.2 °F to 69.7 °F. Nineteen (19)
measurements were below the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
These measurements were collected from the 1st floor. The outdoor temperature measurements
at the playground ranged from 44.0 to 45.2 °F.
Relative Humidity
The relative humidity indoors ranged from 19.0 percent to 28.1 percent. All measurements were
below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity ranged from 20.0 to 21.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 409 ppm to 499 ppm. All CO2
measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations were 420, 435, 430, 435, 435, 440 and 430 ppm. Therefore, the maximum
acceptable level of CO2 at this location was 1140 ppm (background level + 700 ppm). Levels
above the recommended maximum do not indicate a health risk. Carbon dioxide measurements
are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant
respiration. The school building during ATC’s assessment was not occupied.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0
ppm.
Respirable Particulates (PM2
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 11 gg/m^. All
measurements were below the NPAAQS of 65 gg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable
particulate concentration ranged from 10-13 gg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.